Trang chủ / Sản phẩm /

SUNNY CENTRAL 500CP XT / 630CP XT / 720CP XT / 760CP XT

The extended CP XT: more features included

  • Max. permissible DC voltage: 1000 V
  • Nominal AC power (@ 50 °C): 500 kVA / 630 kVA / 720 kVA / 760 kVA

More power: With its extended functions, the new Sunny Central CP XT series is now even more efficient. The reduced specific price, mean that maximum yields are achieved with lower system costs. The Sunny Central CP XT is also optimized for cold temperatures down to -40 °C and with full nominal power in continuous operation up to 50 °C. The inverter includes all grid management functions and is prepared for Q-on-demand. The customized computer platform allows for optimal monitoring and control.


Profitable

  • Up to 1 megawatt system power as standard
  • Significantly reduced specific price thanks to increased power
  • Maximum yields with low system costs

Durable

  • Full nominal power in continuous operation at ambient temperatures up to 50 °C
  • Optimized for extreme climatic conditions between -40 °C and 62 °C
  • Intelligent power management with OptiCool ™

Flexible

  • Wide DC input voltage range for flexible use of various module configurations
  • Perfectly adjusted for the temperature dependent behavior of PV generators

Versatile

  • All grid management functions are included, prepared for & Q-ondemand including pure reactive power operation
  • Customized computer platform for optimal monitoring and control of inverters

Technical Data

Sunny Central 500CP XT

Sunny Central 630CP XT

Input (DC)

Max. DC power (at cos φ =1)

560 kW

713 kW

Max. input voltage

1000 V

1000 V

VMPP_min at IMPP < IDCmax

430 V

500 V

MPP voltage range (at 25°C / at 50°C at 50 Hz)1) 2)

449 V to 850 V / 430 V to 850 V

529 V to 850 V / 500 V to 850 V

MPP voltage range (at 25°C / at 50°C at 60 Hz)1) 2)

449 V to 850 V / 436 V to 850 V

529 V to 850 V / 505 V to 850 V

Rated input voltage

449 V

529 V

Max. input current

1250 A

1350 A

Max. DC short-circuit current

2500 A

2500 A

Number of independent MPP inputs

1

1

Number of DC inputs

9

9

Output (AC)

Rated power (at 25°C) / nominal AC power (at 50°C)

550 kVA / 500 kVA

700 kVA / 630 kVA

Nominal AC voltage / nominal AC voltage range

270 V / 243 V to 310 V

315 V / 284 V to 362 V

AC power frequency / range

50 Hz, 60 Hz / 47 Hz to 63 Hz

50 Hz, 60 Hz / 47 Hz to 63 Hz

Rated power frequency / rated grid voltage

50 Hz / 270 V

50 Hz / 315 V

Max. output current / max. total harmonic distortion

1176 A / 1238 A3) / 0,03

1283 A / 1350 A3) / 0,03

Power factor at rated power / displacement power factor adjustable

1 / 0.9 leading to 0.9 lagging

Feed-in phases / connection phases

3 / 3

3 / 3

Efficiency

Max. efficiency / European efficiency / CEC efficiency

98,6% / 98,4% / 98,5%

98,7% / 98,5% / 98,5%

Protective devices

Input-side disconnection device

Motor-driven load-break switch

Motor-driven load-break switch

Output-side disconnection device

AC circuit breaker

AC circuit breaker

DC overvoltage protection

Type I surge arrester

Type I surge arrester

Lightning protection (according to IEC 62305-1)

Lightning Protection Level III

Lightning Protection Level III

Stand-alone grid detection active / passive

● / —

● / —

Grid monitoring

Ground fault monitoring / remote-controlled ground fault monitoring

○ / ○

○ / ○

Insulation monitoring

Surge arrester for auxiliary power supply

Protection class (according to IEC 62109-1) / overvoltage category (according to IEC 60664-1)

I / III

I / III

General data

Dimensions (W / H / D)

2562 / 2272 / 956 mm (101 / 89 / 38 inches)

Weight in kg

1900 kg / 4200 lb

1900 kg / 4200 lb

Operating temperature range

−25°C to 62°C / −13°F to 144°F

Extended operating temperature range

○  (−40°C to 62°C / −40°F to 144°F)

Noise emission5)

63 db(A)

64 db(A)

Max. self-consumption (operation)6) / self-consumption (night)

1900 W / < 100 W

1900 W / < 100 W

External auxiliary supply voltage

230 V / 400V (3 / N / PE)

230 V / 400V (3 / N / PE)

Cooling concept

OptiCool

OptiCool

Degree of protection: electronics / connection area (according to IEC 60529) / according to IEC 60721-3-4

IP54 / IP43 / 4C2, 4S2

IP54 / IP43 / 4C2, 4S2

Application in unprotected outdoor environments / indoor

● / ○

● / ○

Maximum permissible value for relative humidity (non-condensing)

15% to 95%

15% to 95%

Maximum operating altitude above MSL 2000 m / 4000 m

● / ○

● / ○

Fresh air consumption (inverter)

3000 m3/h

3000 m3/h

 Features

DC connection / AC connection

Ring terminal lug / ring terminal lug

Display

HMI touch display

Communication / protocols

Ethernet (optical fiber optional), Modbus

DC current monitoring (Zone monitoring / String monitoring)

○ / ○

SC-COM / Plant monitoring

●  / ○ (via Sunny Portal)

Color enclosure / door / base / roof

RAL 9016 / 9016 / 7004 / 7004

Guarantee: 5 / 10 / 15 / 20 years

● / ○ / ○ / ○

Configurable grid management functions

Power reduction, reactive power setpoint, dynamic grid support (e.g. LVRT)

Certificates and approvals (more available on request)

 

●  Standard features ○ Optional features — Not available

EN 61000-6-2, EN 61000-6-4, EMC-conformity, CE-conformity,

BDEW-MSRL / FGW / TR8, Arrêté du 23/04/08, R.D. 1663 / 2000, R.D. 661 / 2007, P.O. 12.3 / IEEE 15477)

Type designation

SC 500CP-10

SC 630CP-10

  1. At 1.05 UAC, nom and cos φ = 1
  2. Further AC voltages, DC voltages and power classes can be configured (for more detailed information, see technical information at SMA.de)
  3. up to + 5% Imax possible at VAC < VAC Nom
  4. Efficiency measured without internal power supply
  5. Sound pressure level at a distance of 10 m
  6. Self-consumption at rated operation
  7. Designed and type-tested in accordance with IEEE 1547, serial tests optional available

Technical Data

Sunny Central 720CP XT

Sunny Central 760CP XT

Input (DC)

Max. DC power (at cos φ =1)

808 kW

853 kW

Max. input voltage

1000 V

1000 V

VMPP_min at IMPP < IDCmax

480 V

505 V

MPP voltage range (at 25°C / at 50°C at 50 Hz)1) 2)

577 V to 850 V / 525 V to 850 V

609 V to 850 V / 554 V to 850 V

MPP voltage range (at 25°C / at 50°C at 60 Hz)1) 2)

577 V to 850 V / 525 V to 850 V

609 V to 850 V / 554 V to 850 V

Rated input voltage

577 V

609 V

Max. input current

1400 A

1400 A

Max. DC short-circuit current

2500 A

2500 A

Number of independent MPP inputs

1

1

Number of DC inputs

9

9

Output (AC)

Rated power (at 25°C) / nominal AC power (at 50°C)

792 kVA / 720 kVA

836 kVA / 760 kVA

Nominal AC voltage / nominal AC voltage range

324 V / 292 V to 372 V

342 V / 308 V to 393 V

AC power frequency / range

50 Hz, 60 Hz / 47 Hz to 63 Hz

50 Hz, 60 Hz / 47 Hz to 63 Hz

Rated power frequency / rated grid voltage

50 Hz / 324 V

50 Hz / 342 V

Max. output current / max. total harmonic distortion

1411 A / 0,03

1411 A / 0,03

Power factor at rated power / displacement power factor adjustable

1 / 0.9 leading to 0.9 lagging

Feed-in phases / connection phases

3 / 3

3 / 3

Efficiency

Max. efficiency / European efficiency / CEC efficiency

98,6% / 98,4% / 98,5%

98,6% / 98,4% / 98,5%

Protective devices

Input-side disconnection device

Motor-driven load-break switch

Motor-driven load-break switch

Output-side disconnection device

AC circuit breaker

AC circuit breaker

DC overvoltage protection

Type I surge arrester

Type I surge arrester

Lightning protection (according to IEC 62305-1)

Lightning Protection Level III

Lightning Protection Level III

Stand-alone grid detection active / passive

● / —

● / —

Grid monitoring

Ground fault monitoring / remote-controlled ground fault monitoring

○ / ○

○ / ○

Insulation monitoring

Surge arrester for auxiliary power supply

Protection class (according to IEC 62109-1) / overvoltage category (according to IEC 60664-1)

I / III

I / III

General data

Dimensions (W / H / D)

2562 / 2272 / 956 mm (101 / 89 / 38 inches)

Weight in kg

1900 kg / 4200 lb

1900 kg / 4200 lb

Operating temperature range

−25°C to 62°C / −13°F to 144°F

Extended operating temperature range

○  (−40°C to 62°C / −40°F to 144°F)

Noise emission5)

64 db(A)

64 db(A)

Max. self-consumption (operation)6) / self-consumption (night)

1950 W / < 100 W

1950 W / < 100 W

External auxiliary supply voltage

230 V / 400V (3 / N / PE)

230 V / 400V (3 / N / PE)

Cooling concept

OptiCool

OptiCool

Degree of protection: electronics / connection area (according to IEC 60529) / according to IEC 60721-3-4

IP54 / IP43 / 4C2, 4S2

IP54 / IP43 / 4C2, 4S2

Application in unprotected outdoor environments / indoor

● / ○

● / ○

Maximum permissible value for relative humidity (non-condensing)

15% to 95%

15% to 95%

Maximum operating altitude above MSL 2000 m / 4000 m

● / ○

● / ○

Fresh air consumption (inverter)

3000 m3/h

3000 m3/h

 Features

DC connection / AC connection

Ring terminal lug / ring terminal lug

Display

HMI touch display

Communication / protocols

Ethernet (optical fiber optional), Modbus

DC current monitoring (Zone monitoring / String monitoring)

○ / ○

SC-COM / Plant monitoring

●  / ○ (via Sunny Portal)

Color enclosure / door / base / roof

RAL 9016 / 9016 / 7004 / 7004

Guarantee: 5 / 10 / 15 / 20 years

● / ○ / ○ / ○

Configurable grid management functions

Power reduction, reactive power setpoint, dynamic grid support (e.g. LVRT)

Certificates and approvals (more available on request)

 

●  Standard features ○ Optional features — Not available

EN 61000-6-2, EN 61000-6-4, EMC-conformity, CE-conformity,

BDEW-MSRL / FGW / TR8, Arrêté du 23/04/08, R.D. 1663 / 2000, R.D. 661 / 2007, P.O. 12.3 / IEEE 15477)

Type designation

SC 720CP-10

SC 760CP-10

Sản phẩm khác

  • SUNNY CENTRAL 1000CP XT

    SUNNY CENTRAL 1000CP XT

    The most powerful CP with an output of 1 megawatt

    • Max. permissible DC voltage: 1000 V
    • Nominal AC power (@ 40 °C): 1000 kVA

Hotline: 0919.900.247