  • Max. permissible DC voltage: 1000 V
  • Nominal AC power (@ 40 °C): 1000 kVA

For increased power: With its expanded functions and a peak power of 1100 kVA, the new Sunny Central 1000CP XT is now even more powerful. With its proven technology and high power density, the SC 1000CP XT completes the worldwide most successful Sunny Central CP inverter family for PV. The central inverter for outdoor use is optimized for both full nominal power in continuous operation up to 40 °C and cold temperatures as low as -40 °C. The inverter includes all grid management functions and is prepared for Q at Night, including pure reactive power management. The customized computing platform allows optimal monitoring and control.


Profitable

Robust

Flexible

Versatile

• 1 MW system power as standard

• High power density for reduced

transportation costs

• Maximum yields with low system

costs

• Full nominal power in continuous operation at ambient temperatures up to 40 °C

• Direct installation on-site, optimized

for extreme climatic conditions of

between −40°C and 62°C

• Wide DC input voltage range for flexible use of various module configurations

• Perfectly adjusted to temperature--

dependent behavior of PV arrays

• All grid management functions

included, prepared for Q at Night

• Optimal monitoring and control

thanks to customized computing platform

Technical Data

Sunny Central 1000CP Xt

Input (DC)

Max. DC power (at cos φ =1)

1122 kW

Max. input voltage

1000 V

VMPP_min at IMPP < IDCmax

596 V

MPP voltage range (at 25°C / at 40°C / at 50°C)1) 2)

688 V to 850 V3) / 625 V to 850 V3) / 596 V to 850 V3)

Rated input voltage

688 V

Max. input current

1635 A

Max. DC short-circuit current

2500 A

Number of independent MPP inputs

1

Number of DC inputs

9

Output (aC)

AC power (at 25°C / at 40°C / at 50°C)

1100 kVA / 1000 kVA / 900 kVA

Nominal AC voltage / nominal AC voltage range

405 V / 365 V to 465 V

AC power frequency / range

50 Hz, 60 Hz / 47 Hz to 63 Hz

Rated power frequency / rated grid voltage

50 Hz / 405 V

Max. output current / max. total harmonic distortion

1568 A / 0.03

Power factor at rated power / displacement power factor adjustable

1 / 0.9 overexcited to 0.9 underexcited

Feed-in phases / connection phases

3 / 3

Efficiency

Max. efficiency / European efficiency / CEC efficiency

98.7% / 98.4% / 98.5%

Protective devices

Input-side disconnection device

Motor-driven load-break switch

Output-side disconnection device

AC circuit breaker

DC overvoltage protection

Type I surge arrester

Lightning protection (according to IEC 62305-1)

Lightning Protection Level III

Stand-alone grid detection active / passive

● / —

Grid monitoring

Ground fault monitoring

○ / ○

Insulation monitoring

Surge arrester for auxiliary power supply

Protection class (according to IEC 62109-1) / overvoltage category (according to IEC 60664-1)

I / III

General data

Dimensions (W / H / D)

2562 / 2272 / 956 mm (101 / 89 / 38 inches)

Weight

1900 kg / 4300 lb

Operating temperature range

−25°C to 62°C / −13°F to 144°F

Extended operating temperature range

○ (−40°C to 62°C / −40°F to 144°F)

Noise emission5)

68 db(A)

Max. self-consumption (operation)6) / self-consumption (night)

1950 W / < 100 W

External auxiliary supply voltage

230 V / 400 V (3 / N / PE)

Cooling concept

OptiCool

Degree of protection: electronics / connection area (according to IEC 60529) / according to IEC 60721-3-4

IP54 / IP43 / 4C2, 4S2

Application in unprotected outdoor environments / indoor

● / ○

Maximum permissible value for relative humidity (non-condensing)

15% to 95%

Maximum operating altitude above MSL 2000 m / 4000 m

● / ○

Fresh air consumption (inverter)

3000 m3/h

Features

DC connection / AC connection

Ring terminal lug / ring terminal lug

Display

HMI touch display

Communication / protocols

Ethernet (optical fiber optional), Modbus

DC current monitoring (Zone monitoring / String monitoring)

○ / ○

SC-COM / Plant monitoring

●  / ○ (via Sunny Portal)

Color enclosure / door / base / roof

RAL 9016 / 9016 / 7004 / 7004

Guarantee: 5 / 10 / 15 / 20 years

● / ○ / ○ / ○

Configurable grid management functions

Power reduction, reactive power setpoint, dynamic grid support (e.g. LVRT)

Certificates and approvals (more available on request)

EN 61000-6-2, EN 61000-6-4, EMC-conformity, CE-conformity,

BDEW-MSRL / FGW / TR8, Arrêté du 23/04/08, R.D. 1663 / 2000, R.D. 661 / 2007, P.O. 12.3 / IEEE 15477)