SUNNY CENTRAL 500CP-JP / 630CP-JP / 800CP-JP / 1000CP-JP
The perfect solution for PV power plants in Japan
- Max. input voltage: 1000 V
- Nominal AC power (@ 50 °C): 455 kVA / 630 kVA / 800 kVA / 900 kVA
The durable and high-performance Sunny Central 1000CP-JP guarantees maximum yields in all climate zones. This has been clearly demonstrated in numerous stress tests. With the integrated OptiCool™ cooling system, the Sunny Central 1000CP-JP can continue to feed solar power into the power distribution grid even at ambient temperatures up to 62 °C. The compact and durable enclosure for the equipment allows easy and uncomplicated outdoor installation – without complex enclosures and external cooling systems. This significantly reduces costs and self-consumption. With its comprehensive grid management functions, the Sunny Central 1000CP-JP already fulfills future requirements for grid operators.
Outdoor
- Compact and weatherproof enclosure for outdoor installation
- OptiCool™ cooling system for ambient temperatures of up to 62 °C
Efficient
- Peak efficiency of 98.6 %
- Higher profit thanks to low self-consumption
Durable
- Resistant to salt corrosion
- Resists sand and dust
- Suitable for all climate zones
Reliable
- High operational safety and easy to maintain
- Powerful grid management functions (including FRT)
Technical data |
Sunny Central 630CP-JP |
Sunny Central 500CP-JP |
|
Input (DC) |
|||
Max. DC power (at cos φ = 1) |
713 kW |
511 kW |
|
Max. input voltage |
1000 V |
600 V |
|
MPP voltage range (50 Hz) / MPP voltage range (60 Hz) |
500 V to 850 V¹) / 505 V to 850 V¹) |
332 V to 600 V¹) / 332 V to 600 V¹) |
|
DC voltage range (50 Hz) / DC voltage range (60 Hz) |
500 V to 850 V / 500 V to 850 V |
311 V to 600 V / 321 V to 600 V |
|
Rated input voltage |
529 V |
365 V |
|
Max. input current |
1350 A |
1400 A |
|
Max. short-circuit current |
2500 A |
2500 A |
|
VMPPmin at IMPP < IDCmax |
500 V (50 Hz) / 500 V (60 Hz) |
311 V (50 Hz) / 321 V (60 Hz) |
|
Number of independent MPP inputs |
1 |
1 |
|
Number of DC inputs |
9 |
9 |
|
Output (aC) |
|||
Rated power (at 25°C) / Nominal AC power (at 50°C) |
700 kVA / 473 kVA |
500 kVA / 341 kVA |
|
AC nominal voltage / range |
315 V / 284 V to 362 V |
205 V / 185 V to 235 V |
|
AC frequency / range |
50 Hz, 60 Hz / 47 Hz to 63 Hz |
50 Hz, 60 Hz / 47 Hz to 63 Hz |
|
Rated frequency / rated grid voltage |
50 Hz / 315 V |
50 Hz / 205 V |
|
Max. output current |
1283 A / 1350 A6) |
1411 A |
|
Max. THD |
< 3 % |
< 3 % |
|
Power factor at rated power/adjustable shift factor |
1 / 0.9 leading to 0.9 lagging |
1 / 0.9 leading to 0.9 lagging |
|
Feed-in phases / connection phases |
3 / 3 |
3 / 3 |
|
Efficiency |
|||
Max. efficiency / European weighted efficiency / CEC efficiency |
98.1 % / 97.8 % / 98.0 % |
98.0 % / 97.6 % / 97.5 % |
|
Protective devices |
|||
Input-side disconnection device |
Motor-driven DC switch disconnector |
Motor-driven DC switch disconnector |
|
Output-side disconnection device |
AC circuit breaker |
AC circuit breaker |
|
DC overvoltage protection |
Type I surge arrester |
Type I surge arrester |
|
Lightning protection (according to IEC 62305-1) |
Lightning protection level III |
Lightning protection level III |
|
Grid monitoring |
● |
● |
|
Stand-alone grid detection |
active, passive |
active, passive |
|
Ground-fault monitoring/remote-controlled ground-fault monitoring |
○ / ○ |
○ / ○ |
|
Insulation Monitoring |
○ |
○ |
|
Surge arrester for communication interface/string current monitoring |
○ / ○ |
○ / ○ |
|
Surge arrester for auxiliary supply |
Type I and type II surge arrester |
Type I and type II surge arrester |
|
Protection class (according to IEC 62109-1) / overvoltage category (according to IEC 60664-1) |
I / III |
I / III |
|
General data |
|||
Dimensions (W / H / D) |
2562 / 2272 / 1210 mm |
2562 / 2272 / 1210 mm |
|
Weight |
1822 kg |
1822 kg |
|
Operating temperature range |
−25°C to +62°C |
−25°C to +62°C |
|
Noise emission³) |
53 db(A) |
53 db(A) |
|
Max. self-consumption (operation)4) / consumption (night) |
1900 W / < 100 W |
1950 W / < 100 W |
|
External auxiliary supply voltage |
230 / 400 V (3/N/PE) |
230 / 400 V (3/N/PE) |
|
Cooling concept |
Opticool |
Opticool |
|
Degree of protection: electronics / connection area (according to IEC 60529 / to IEC 60721-3-4) |
IP54 / IP43 / 4C2, 4S2 |
IP54 / IP43 / 4C2, 4S2 |
|
Application |
In unprotected outdoor environments |
In unprotected outdoor environments |
|
Max. permissible value for relative humidity (non-condensing) |
15 % to 95 % |
15 % to 95 % |
|
Max. operating altitude above MSL |
2000 m |
2000 m |
|
Fresh-air consumption |
3000 m³/h |
3000 m³/h |
|
Features |
|||
DC connection / AC connection |
Ring terminal lug / Ring terminal lug |
Ring terminal lug / Ring terminal lug |
|
Display |
HMI touchscreen |
HMI touchscreen |
|
Communication protocols |
Ethernet (optical fiber optional), Modbus |
Ethernet (optical fiber optional), Modbus |
|
DC current monitoring (Zone monitoring / String monitoring) |
○ / ○ |
○ / ○ |
|
Color enclosure, door, base, roof, silencer |
RAL 9016 / 9016 / 7004 / 7004 / 7035 |
RAL 9016 / 9016 / 7004 / 7004 / 7035 |
|
Configurable grid management functions |
Power reduction, reactive power setpoint, dynamic grid support (e.g. FRT) |
Power reduction, reactive power setpoint, dynamic grid support (e.g. FRT) |
|
Certificates and approvals (additional on request) |
EN 61000-6-2, EN 61000-6-4, CE-conformity, Renewable Energy Source Act-compliant, BDEW-MSRL / JETGR0002-1-2.0 (2011) / JETGR0003-1-2.0 (2011)5), Arrêté du 23/04/08, R.D. 1663 / 2000, R.D. 661 / 2007 |
EN 61000-6-2, EN 61000-6-4, CE-conformity, Renewable Energy Source Act-compliant, BDEW-MSRL / JETGR0002-1-2.0 (2011) / JETGR0003-1-2.0 (2011)5), Arrêté du 23/04/08, R.D. 1663 / 2000, R.D. 661 / 2007 |
|
● Standard feature ○ Optional feature — Not available |
|
|
|
Type designation |
SC 630CP-10-JP |
SC 500CP-10-JP |
Technical Data |
Sunny Central 800CP-JP |
Sunny Central 1000CP-JP* |
Input (DC)
Max. convertable DC power (at cos φ =1) |
898 kW |
1122 kW |
Max. input voltage |
1000 V |
1000 V |
MPP voltage range (50 Hz) / MPP voltage range (60 Hz) |
583 V to 850 V¹) / 583 V to 850 V¹) |
625 V to 850 V¹) / 625 V to 850 V¹) |
DC voltage range (50 Hz) / DC voltage range (60 Hz) |
530 V to 850 V / 530 V to 850 V |
596 V to 850 V / 596 V to 850 V |
Rated input voltage |
641 V |
688 V |
Max. input current |
1400 A |
1635 A |
Max. DC short-circuit current |
2500 A |
2500 A |
VMPPmin at IMPP < IDCmax |
530 V (50 Hz) / 530 V (60 Hz) |
596 V (50 Hz) / 596 V (60 Hz) |
Number of independent MPP inputs |
1 |
1 |
Number of DC inputs |
9 |
9 |
Output (aC)
Rated power (at 25°C / at 50°C) |
880 kVA / 800 kVA |
|
AC power (at 25°C / at 40°C / at 50°C) |
|
1100 kVA / 1000 kVA / 900 kVA |
AC nominal voltage / AC nominal voltage range |
360 V / 324 V to 414 V |
405 V / 365 V to 465 V |
AC frequency / AC frequency range |
50 Hz, 60 Hz / 47 Hz to 63 Hz |
50 Hz, 60 Hz / 47 Hz to 63 Hz |
Rated frequency / rated grid voltage |
50 Hz / 360 V |
50 Hz / 405 V |
Max. output current |
1411 A |
1568 A |
Max. THD |
< 3 % |
< 3 % |
Power factor at rated power / adjustable shift factor |
1 / 0.9 overexcited to 0.9 underexcited |
1 / 0.9 overexcited to 0.9 underexcited |
Feed-in phases / connection phases |
3 / 3 |
3 / 3 |
Efficiency2)
Max. efficiency / European efficiency / CEC efficiency |
98.6 % / 98.4 % / 98.5 % |
98.7% / 98.4% / 98.5% |
Protective devices
Input-side disconnection device |
Motor-driven load-break switch |
Motor-driven load-break switch |
Output-side disconnection device |
AC circuit breaker |
AC circuit breaker |
DC overvoltage protection |
Type I surge arrester |
Type I surge arrester |
Lightning protection (according to IEC 62305-1) |
Lightning protection level III |
Lightning protection level III |
Grid monitoring |
● |
● |
Stand-alone grid detection active / passive |
● / ● |
● / ● |
Ground fault monitoring / remote-controlled ground-fault monitoring |
○ / ○ |
○ / ○ |
Insulation monitoring |
○ |
○ |
Surge arrester for communication interface / string current monitoring |
○ / ○ |
○ / ○ |
Surge arrester for auxiliary supply |
Type I and type II surge arrester |
Type I and type II surge arrester |
Protection class (according to IEC 62109-1) / overvoltage category (ac- cording to IEC 60664-1) |
I / III |
I / III |
General data
Dimensions (W / H / D) |
2562 / 2272 / 956 mm (101 / 89 / 38 inches) |
|
Weight |
approx. 1800 kg |
approx. 1800 kg |
Operating temperature range |
−25°C to 62°C / −13°F to 144°F |
−25°C to 62°C / −13°F to 144°F |
Extended operating temperature range |
○ (−40°C to 62°C / −40°F to 144°F) |
○ (−40°C to 62°C / −40°F to 144°F) |
Noise emission3) |
64 db(A) |
68 db(A) |
Max. self-consumption (operation)4) / self-consumption (night) |
1950 W / < 100 W |
1950 W / < 100 W |
External auxiliary supply voltage |
230 V / 400 V (3 / N / PE) |
230 V / 400 V (3 / N / PE) |
Cooling concept |
OptiCool |
OptiCool |
Degree of protection: electronics / connection area (according to IEC 60529) / according to IEC 60721-3-4 |
IP54 / IP43 / 4C2, 4S2 |
IP54 / IP43 / 4C2, 4S2 |
Application |
In unprotected outdoor environments |
In unprotected outdoor environments |
Maximum permissible value for relative humidity (non-condensing) |
15% to 95% |
15% to 95% |
Maximum operating altitude above MSL |
2000 m |
2000 m |
Fresh air consumption (inverter) |
3000 m3/h |
3000 m3/h |
Features
DC connection / AC connection |
Ring terminal lug / ring terminal lug |
Ring terminal lug / ring terminal lug |
Display |
HMI touch display |
HMI touch display |
Communication / protocols |
Ethernet (optical fiber optional), Modbus |
Ethernet (optical fiber optional), Modbus |
DC current monitoring (Zone monitoring / String monitoring) |
○ / ○ |
○ / ○ |
Color enclosure / door / base / roof |
RAL 9016 / 9016 / 7004 / 7004 |
RAL 9016 / 9016 / 7004 / 7004 |
Configurable grid management functions |
Power reduction, reactive power setpoint, dynamic grid support (e.g. LVRT) |
|
Certificates and approvals (additional on request) |
EN 61000-6-2, EN 61000-6-4, CE-conformity, Renewable Energy Source Act-compliant, BDEW- MSRL / JETGR0002-1-2.0 (2011) / JETGR0003-1-2.0 (2011)5), Arrêté du 23/04/08, R.D. 1663 / 2000, R.D. 661 / 2007 |
|
● Standard features ○ Optional features — Not available * all the data for SC 1000 CP-JP are provisional |
|
|
|
|
|
Type designation |
SC 800CP-10-JP |
SC 1000CP-10-JP |
Sản phẩm khác
-
SUNNY CENTRAL UP
The new Sunny Central: more power per cubic meter
-
SUNNY CENTRAL 2200 / 2475 / 2500-EV / 2750-EV / 3000-EV
The new Sunny Central: more power per cubic meter
-
SUNNY CENTRAL 1850-US / 2200-US / 2500-EV-US / 2750-EV-US
Maximum power density and integration
-
SUNNY CENTRAL 1000CP XT
The most powerful CP with an output of 1 megawatt
- Max. permissible DC voltage: 1000 V
- Nominal AC power (@ 40 °C): 1000 kVA
-
SUNNY CENTRAL 800CP XT / 850CP XT / 900CP XT
The extended CP XT: peak output up to 1 megawatt
- Max. permissible DC voltage: 1000 V
- Nominal AC power (@ 50 °C): 800 kVA / 850 kVA / 900 kVA
-
SUNNY CENTRAL 500CP XT / 630CP XT / 720CP XT / 760CP XT
The extended CP XT: more features included
- Max. permissible DC voltage: 1000 V
- Nominal AC power (@ 50 °C): 500 kVA / 630 kVA / 720 kVA / 760 kVA