Home / Products /

SUNNY CENTRAL 500CP-JP / 630CP-JP / 800CP-JP / 1000CP-JP

The perfect solution for PV power plants in Japan

  • Max. input voltage: 1000 V
  • Nominal AC power (@ 50 °C): 455 kVA / 630 kVA / 800 kVA / 900 kVA

The durable and high-performance Sunny Central 1000CP-JP guarantees maximum yields in all climate zones. This has been clearly demonstrated in numerous stress tests. With the integrated OptiCool™ cooling system, the Sunny Central 1000CP-JP can continue to feed solar power into the power distribution grid even at ambient temperatures up to 62 °C. The compact and durable enclosure for the equipment allows easy and uncomplicated outdoor installation – without complex enclosures and external cooling systems. This significantly reduces costs and self-consumption. With its comprehensive grid management functions, the Sunny Central 1000CP-JP already fulfills future requirements for grid operators.


Outdoor

  • Compact and weatherproof enclosure for outdoor installation
  • OptiCool™ cooling system for ambient temperatures of up to 62 °C

Efficient

  • Peak efficiency of 98.6 %
  • Higher profit thanks to low self-consumption

Durable

  • Resistant to salt corrosion
  • Resists sand and dust
  • Suitable for all climate zones

Reliable

  • High operational safety and easy to maintain
  • Powerful grid management functions (including FRT)

Technical data

Sunny Central 630CP-JP

Sunny Central 500CP-JP

Input (DC)

Max. DC power (at cos φ = 1)

713 kW

511 kW

Max. input voltage

1000 V

600 V

MPP voltage range (50 Hz) / MPP voltage range (60 Hz)

500 V to 850 V¹) / 505 V to 850 V¹)

332 V to 600 V¹) / 332 V to 600 V¹)

DC voltage range (50 Hz) / DC voltage range (60 Hz)

500 V to 850 V / 500 V to 850 V

311 V to 600 V / 321 V to 600 V

Rated input voltage

529 V

365 V

Max. input current

1350 A

1400 A

Max. short-circuit current

2500 A

2500 A

VMPPmin at IMPP < IDCmax

500 V (50 Hz) / 500 V (60 Hz)

311 V (50 Hz) / 321 V (60 Hz)

Number of independent MPP inputs

1

1

Number of DC inputs

9

9

Output (aC)

Rated power (at 25°C) / Nominal AC power (at 50°C)

700 kVA / 473 kVA

500 kVA / 341 kVA

AC nominal voltage / range

315 V / 284 V to 362 V

205 V / 185 V to 235 V

AC frequency / range

50 Hz, 60 Hz / 47 Hz to 63 Hz

50 Hz, 60 Hz / 47 Hz to 63 Hz

Rated frequency / rated grid voltage

50 Hz / 315 V

50 Hz / 205 V

Max. output current

1283 A / 1350 A6)

1411 A

Max. THD

< 3 %

< 3 %

Power factor at rated power/adjustable shift factor

1 / 0.9 leading to 0.9 lagging

1 / 0.9 leading to 0.9 lagging

Feed-in phases / connection phases

3 / 3

3 / 3

Efficiency

Max. efficiency / European weighted efficiency / CEC efficiency

98.1 % / 97.8 % / 98.0 %

98.0 % / 97.6 % / 97.5 %

Protective devices

Input-side disconnection device

Motor-driven DC switch disconnector

Motor-driven DC switch disconnector

Output-side disconnection device

AC circuit breaker

AC circuit breaker

DC overvoltage protection

Type I surge arrester

Type I surge arrester

Lightning protection (according to IEC 62305-1)

Lightning protection level III

Lightning protection level III

Grid monitoring

Stand-alone grid detection

active, passive

active, passive

Ground-fault monitoring/remote-controlled ground-fault monitoring

○ / ○

○ / ○

Insulation Monitoring

Surge arrester for communication interface/string current monitoring

○ / ○

○ / ○

Surge arrester for auxiliary supply

Type I and type II surge arrester

Type I and type II surge arrester

Protection class (according to IEC 62109-1) / overvoltage category (according to IEC 60664-1)

I / III

I / III

General data

Dimensions (W / H / D)

2562 / 2272 / 1210 mm

2562 / 2272 / 1210 mm

Weight

1822 kg

1822 kg

Operating temperature range

−25°C to +62°C

−25°C to +62°C

Noise emission³)

53 db(A)

53 db(A)

Max. self-consumption (operation)4) / consumption (night)

1900 W / < 100 W

1950 W / < 100 W

External auxiliary supply voltage

230 / 400 V (3/N/PE)

230 / 400 V (3/N/PE)

Cooling concept

Opticool

Opticool

Degree of protection: electronics / connection area (according to IEC 60529 / to IEC 60721-3-4)

IP54 / IP43 / 4C2, 4S2

IP54 / IP43 / 4C2, 4S2

Application

In unprotected outdoor environments

In unprotected outdoor environments

Max. permissible value for relative humidity (non-condensing)

15 % to 95 %

15 % to 95 %

Max. operating altitude above MSL

2000 m

2000 m

Fresh-air consumption

3000 m³/h

3000 m³/h

Features 

DC connection / AC connection

Ring terminal lug / Ring terminal lug

Ring terminal lug / Ring terminal lug

Display

HMI touchscreen

HMI touchscreen

Communication protocols

Ethernet (optical fiber optional), Modbus

Ethernet (optical fiber optional), Modbus

DC current monitoring (Zone monitoring / String monitoring)

○ / ○

○ / ○

Color enclosure, door, base, roof, silencer

RAL 9016 / 9016 / 7004 / 7004 / 7035

RAL 9016 / 9016 / 7004 / 7004 / 7035

Configurable grid management functions

Power reduction, reactive power setpoint, dynamic grid support (e.g. FRT)

Power reduction, reactive power setpoint, dynamic grid support (e.g. FRT)

Certificates and approvals (additional on request)

EN 61000-6-2, EN 61000-6-4, CE-conformity, Renewable Energy Source Act-compliant, BDEW-MSRL / JETGR0002-1-2.0 (2011) / JETGR0003-1-2.0

(2011)5), Arrêté du 23/04/08, R.D. 1663 / 2000, R.D. 661 / 2007

EN 61000-6-2, EN 61000-6-4, CE-conformity, Renewable Energy Source Act-compliant, BDEW-MSRL / JETGR0002-1-2.0 (2011) / JETGR0003-1-2.0

(2011)5), Arrêté du 23/04/08, R.D. 1663 / 2000, R.D. 661 / 2007

●  Standard feature ○ Optional feature — Not available

 

 

Type designation

SC 630CP-10-JP

SC 500CP-10-JP

 

Technical Data

Sunny Central 800CP-JP

Sunny Central 1000CP-JP*

Input (DC)

Max. convertable DC power (at cos φ =1)

898 kW

1122 kW

Max. input voltage

1000 V

1000 V

MPP voltage range (50 Hz) / MPP voltage range (60 Hz)

583 V to 850 V¹) / 583 V to 850 V¹)

625 V to 850 V¹) / 625 V to 850 V¹)

DC voltage range (50 Hz) / DC voltage range (60 Hz)

530 V to 850 V / 530 V to 850 V

596 V to 850 V / 596 V to 850 V

Rated input voltage

641 V

688 V

Max. input current

1400 A

1635 A

Max. DC short-circuit current

2500 A

2500 A

VMPPmin at IMPP < IDCmax

530 V (50 Hz) / 530 V (60 Hz)

596 V (50 Hz) / 596 V (60 Hz)

Number of independent MPP inputs

1

1

Number of DC inputs

9

9

Output (aC)

Rated power (at 25°C / at 50°C)

880 kVA / 800 kVA

 

AC power (at 25°C / at 40°C / at 50°C)

 

1100 kVA / 1000 kVA / 900 kVA

AC nominal voltage / AC nominal voltage range

360 V / 324 V to 414 V

405 V / 365 V to 465 V

AC frequency / AC frequency range

50 Hz, 60 Hz / 47 Hz to 63 Hz

50 Hz, 60 Hz / 47 Hz to 63 Hz

Rated frequency / rated grid voltage

50 Hz / 360 V

50 Hz / 405 V

Max. output current

1411 A

1568 A

Max. THD

< 3 %

< 3 %

Power factor at rated power / adjustable shift factor

1 / 0.9 overexcited to 0.9 underexcited

1 / 0.9 overexcited to 0.9 underexcited

Feed-in phases / connection phases

3 / 3

3 / 3

Efficiency2)

Max. efficiency / European efficiency / CEC efficiency

98.6 % / 98.4 % / 98.5 %

98.7% / 98.4% / 98.5%

Protective devices

Input-side disconnection device

Motor-driven load-break switch

Motor-driven load-break switch

Output-side disconnection device

AC circuit breaker

AC circuit breaker

DC overvoltage protection

Type I surge arrester

Type I surge arrester

Lightning protection (according to IEC 62305-1)

Lightning protection level III

Lightning protection level III

Grid monitoring

Stand-alone grid detection active / passive

● / ●

● / ●

Ground fault monitoring / remote-controlled ground-fault monitoring

○ / ○

○ / ○

Insulation monitoring

Surge arrester for communication interface / string current monitoring

○ / ○

○ / ○

Surge arrester for auxiliary supply

Type I and type II surge arrester

Type I and type II surge arrester

Protection class (according to IEC 62109-1) / overvoltage category (ac-

cording to IEC 60664-1)

I / III

I / III

General data

Dimensions (W / H / D)

2562 / 2272 / 956 mm (101 / 89 / 38 inches)

Weight

approx. 1800 kg

approx. 1800 kg

Operating temperature range

−25°C to 62°C / −13°F to 144°F

−25°C to 62°C / −13°F to 144°F

Extended operating temperature range

○  (−40°C to 62°C / −40°F to 144°F)

○  (−40°C to 62°C / −40°F to 144°F)

Noise emission3)

64 db(A)

68 db(A)

Max. self-consumption (operation)4) / self-consumption (night)

1950 W / < 100 W

1950 W / < 100 W

External auxiliary supply voltage

230 V / 400 V (3 / N / PE)

230 V / 400 V (3 / N / PE)

Cooling concept

OptiCool

OptiCool

Degree of protection: electronics / connection area (according to IEC

60529) / according to IEC 60721-3-4

IP54 / IP43 / 4C2, 4S2

IP54 / IP43 / 4C2, 4S2

Application

In unprotected outdoor environments

In unprotected outdoor environments

Maximum permissible value for relative humidity (non-condensing)

15% to 95%

15% to 95%

Maximum operating altitude above MSL

2000 m

2000 m

Fresh air consumption (inverter)

3000 m3/h

3000 m3/h

Features

DC connection / AC connection

Ring terminal lug / ring terminal lug

Ring terminal lug / ring terminal lug

Display

HMI touch display

HMI touch display

Communication / protocols

Ethernet (optical fiber optional), Modbus

Ethernet (optical fiber optional), Modbus

DC current monitoring (Zone monitoring / String monitoring)

○ / ○

○ / ○

Color enclosure / door / base / roof

RAL 9016 / 9016 / 7004 / 7004

RAL 9016 / 9016 / 7004 / 7004

Configurable grid management functions

Power reduction, reactive power setpoint, dynamic grid support (e.g. LVRT)

Certificates and approvals (additional on request)

EN 61000-6-2, EN 61000-6-4, CE-conformity, Renewable Energy Source Act-compliant, BDEW-

MSRL / JETGR0002-1-2.0 (2011) / JETGR0003-1-2.0 (2011)5),

Arrêté du 23/04/08, R.D. 1663 / 2000, R.D. 661 / 2007

●  Standard features ○ Optional features — Not available

* all the data for SC 1000 CP-JP are provisional

 

 

 

 

 

Type designation

SC 800CP-10-JP

SC 1000CP-10-JP

Other

  • SUNNY CENTRAL 1000CP XT

    SUNNY CENTRAL 1000CP XT

    The most powerful CP with an output of 1 megawatt

    • Max. permissible DC voltage: 1000 V
    • Nominal AC power (@ 40 °C): 1000 kVA

Hotline: (+84) 919.900.247