SUNNY CENTRAL 2200 / 2475 / 2500-EV / 2750-EV / 3000-EV
The new Sunny Central: more power per cubic meter
The Sunny Central inverter, with 1,850 kVA or 2,200 kVA for 1,000 VDC and 2,500 kVA, 2,750 kVA or 3,000 kVA for 1,500 VDC (at 35°C), enables even more efficient PV power plant designs. The flexibility of this inverter allows for implementation with a variety of modules. The integrated power supply transformer and installation area provide an ideal environment for integration of needed customer equipment. Suitable for any outdoor climate around the globe, this new Sunny Central is equipped with OptiCool, a proven air-cooling technology that ensures smooth operation under extreme environmental conditions.
Efficient
- Up to 4 inverters can be transported in one standard shipping container
- Overdimensioning up to 225% is possible
- Full power at ambient temperatures of up to 35°C
Robust
- Intelligent air cooling system OptiCool for efficient cooling
- Suitable for outdoor use in all climatic ambient conditions worldwide
Flexible
- Conforms to all known grid requirements worldwide
- Q on demand
- Available as a single device or turnkey solution, including medium-voltage block
Easy to Use
- Improved DC connection area
- Connection area for customer equipment
- Integrated voltage support for internal and external loads
Technical Data |
Sunny Central 2200 |
Sunny Central 2475* |
Input (DC)
MPP voltage range VDC (at 25 °C / at 35 °C / at 50 °C) |
570 to 950 V / 800 V / 800 V |
638 V to 950 V / 800 V / 800 V |
Min. input voltage VDC, min / Start voltage VDC, Start |
545 V / 645 V |
614 V / 714 V |
Max. input voltage VDC, max |
1100 V |
1100 V |
Max. input current IDC, max (at 35°C / at 50°C) |
3960 A / 3600 A |
3960 A / 3600 A |
Max. short-circuit current IDC, sc |
6400 A |
6400 A |
Number of DC inputs |
24 double pole fused (32 single pole fused) |
|
Max. number of DC cables per DC input (for each polarity) |
2 x 800 kcmil, 2 x 400 mm² |
|
Integrated zone monitoring |
○ |
|
Available DC fuse sizes (per input) |
200 A, 250 A, 315 A, 350 A, 400 A, 450 A, 500 A |
Output (AC)
Nominal AC power at cos φ =1 (at 35°C / at 50°C) |
2200 kVA / 2000 kVA |
2475 kVA / 2250 kVA |
Nominal AC power at cos φ =0.8 (at 35°C / at 50°C) |
1760 kW / 1600 kW |
1980 kW / 1800 kW |
Nominal AC current IAC, nom = Max. output current IAC, max |
3300 A |
3300 A |
Max. total harmonic distortion |
< 3% at nominal power |
< 3% at nominal power |
Nominal AC voltage / nominal AC voltage range1) 8) |
385 V / 308 V to 462 V |
434 V / 347 V to 521 V |
AC power frequency / range |
50 Hz / 47 Hz to 53 Hz 60 Hz / 57 Hz to 63 Hz |
|
Min. short-circuit ratio at the AC terminals9) |
> 2 |
|
Power factor at rated power / displacement power factor adjustable8) 10) |
● 1 / 0.8 overexcited to 0.8 underexcited ○ 1 / 0.0 overexcited to 0.0 underexcited |
Efficiency
Max. efficiency2) / European efficiency2) / CEC efficiency3) |
98.6% / 98.4% / 98.0% |
98.6% / 98.4% / 98.0% |
Protective Devices
Input-side disconnection point |
DC load break switch |
Output-side disconnection point |
AC circuit breaker |
DC overvoltage protection |
Surge arrester, type I |
AC overvoltage protection (optional) |
Surge arrester, class I |
Lightning protection (according to IEC 62305-1) |
Lightning Protection Level III |
Ground-fault monitoring / remote ground-fault monitoring |
○ / ○ |
Insulation monitoring |
○ |
Degree of protection: electronics / air duct / connection area (as per IEC 60529) |
IP65 / IP34 / IP34 |
General Data
Dimensions (W / H / D) |
2780 / 2318 / 1588 mm (109.4 / 91.3 / 62.5 inch) |
Weight |
< 3400 kg / < 7496 lb |
Self-consumption (max.4) / partial load5) / average6)) |
< 8100 W / < 1800 W / < 2000 W |
Self-consumption (standby) |
< 300 W |
Internal auxiliary power supply |
Integrated 8.4 kVA transformer |
Operating temperature range8) |
−25°C to 60°C / −13°F to 140°F |
Noise emission7) |
67.0 dB(A) |
Temperature range (standby) |
−40°C to 60°C / −40°F to 140°F |
Temperature range (storage) |
−40°C to 70°C / −40°F to 158°F |
Max. permissible value for relative humidity (condensing / non-condensing) |
95% to 100% (2 month/year) / 0% to 95% |
Maximum operating altitude above MSL8) 1000 m / 2000 m / 3000 m / 4000 m |
● / ○ / ○ / ○ (earlier temperature-dependent derating) |
Fresh air consumption |
6500 m³/h |
Features
DC connection |
Terminal lug on each input (without fuse) |
|
AC connection |
With busbar system (three busbars, one per line conductor) |
|
Communication |
Ethernet, Modbus Master, Modbus Slave |
|
Communication with SMA string monitor (transmission medium) |
Modbus TCP / Ethernet (FO MM, Cat-5) |
|
Enclosure / roof color |
RAL 9016 / RAL 7004 |
|
Supply transformer for external loads |
○ (2.5 kVA) |
|
Standards and directives complied with |
CE, IEC / EN 62109-1, IEC / EN 62109-2, BDEW-MSRL, IEEE1547, UL 840 Cat. IV, Arrêté du 23/04/08 |
|
EMC standards |
IEC / EN 61000-6-4, IEC / EN 61000-6-2, EN 55022, IEC 62920, FCC Part 15 Class A, Cispr 11, DIN EN55011:2017 |
|
Quality standards and directives complied with |
VDI/VDE 2862 page 2, DIN EN ISO 9001 |
|
● Standard features ○ Optional * preliminary |
|
|
Type designation |
SC-2200-10 |
SC-2475-10 |
- At nominal AC voltage, nominal AC power decreases in the same proportion
- Efficiency measured without internal power supply
- Efficiency measured with internal power supply
- Self-consumption at rated operation
- Self-consumption at < 75% Pn at 25°C
- Self-consumption averaged out from 5% to 100% Pn at 25°C
- Sound pressure level at a distance of 10 m
- Values apply only to Permissible values for SMA MV solutions from SMA can be found in the corresponding data sheets.
- A short-circuit ratio of < 2 requires a special approval from SMA
- Depending on the DC voltage
Technical Data |
Sunny Central 2500-EV |
Sunny Central 2750-EV |
Sunny Central 3000-EV |
Input (DC)
MPP voltage range VDC (at 25°C / at 35°C / at 50°C) |
850 V to 1425 V / 1200 V / 1200 V |
875 V to 1425 V / 1200 V / 1200 V |
956 V to 1425 V / 1200 V / 1200 V |
Min. input voltage VDC, min / Start voltage VDC, Start |
778 V / 928 V |
849 V / 999 V |
927 V / 1077 V |
Max. input voltage VDC, max |
1500 V |
1500 V |
1500 V |
Max. input current IDC, max (at 35°C / at 50°C) |
3200 A / 2956 A |
3200 A / 2956 A |
3200 A / 2970 A |
Max. short-circuit current rating |
6400 A |
6400 A |
6400 A |
Number of DC inputs |
24 double pole fused (32 single pole fused) for PV |
||
Number of DC inputs with optional DC battery coupling |
18 double pole fused (36 single pole fused) for PV and 6 double pole fused for batteries |
||
Max. number of DC cables per DC input (for each polarity) |
2 x 800 kcmil, 2 x 400 mm² |
||
Integrated zone monitoring |
○ |
||
Available DC fuse sizes (per input) |
200 A, 250 A, 315 A, 350 A, 400 A, 450 A, 500 A |
Output (AC)
Nominal AC power at cos φ =1 (at 35°C / at 50°C) |
2500 kVA / 2250 kVA |
2750 kVA / 2500 kVA |
3000 kVA / 2700 kVA |
Nominal AC power at cos φ =0.8 (at 35°C / at 50°C) |
2000 kW / 1800 kW |
2200 kW / 2000 kW |
2400 kW / 2160 kW |
Nominal AC current IAC, nom = Max. output current IAC, max |
2624 A |
2646 A |
2646 A |
Max. total harmonic distortion |
< 3% at nominal power |
< 3% at nominal power |
< 3% at nominal power |
Nominal AC voltage / nominal AC voltage range1) 8) |
550 V / 440 V to 660 V |
600 V / 480 V to 690 V |
655 V / 524 V to 721 V9) |
AC power frequency |
50 Hz / 47 Hz to 53 Hz 60 Hz / 57 Hz to 63 Hz |
||
Min. short-circuit ratio at the AC terminals10) |
> 2 |
||
Power factor at rated power / displacement power factor adjustable8) 11) |
● 1 / 0.8 overexcited to 0.8 underexcited ○ 1 / 0.0 overexcited to 0.0 underexcited |
Efficiency
Max. efficiency2) / European efficiency2) / CEC efficiency3) |
98.6% / 98.3% / 98.0% |
98.7% / 98.5% / 98.5% |
98.8% / 98.6% / 98.5% |
Protective Devices
Input-side disconnection point |
DC load-break switch |
Output-side disconnection point |
AC circuit breaker |
DC overvoltage protection |
Surge arrester, type I |
AC overvoltage protection (optional) |
Surge arrester, class I |
Lightning protection (according to IEC 62305-1) |
Lightning Protection Level III |
Ground-fault monitoring / remote ground-fault monitoring |
○ / ○ |
Insulation monitoring |
○ |
Degree of protection: electronics / air duct / connection area (as per IEC 60529) |
IP65 / IP34 / IP34 |
General Data
Dimensions (W / H / D) |
2780 / 2318 / 1588 mm (109.4 / 91.3 / 62.5 inch) |
Weight |
< 3400 kg / < 7496 lb |
Self-consumption (max.4) / partial load5) / average6)) |
< 8100 W / < 1800 W / < 2000 W |
Self-consumption (standby) |
< 370 W |
Internal auxiliary power supply |
Integrated 8.4 kVA transformer |
Operating temperature range8) |
−25 to 60°C / −13 to 140°F |
Noise emission7) |
67.8 dB(A) |
Temperature range (standby) |
−40 to 60°C / −40 to 140°F |
Temperature range (storage) |
−40 to 70°C / −40 to 158°F |
Max. permissible value for relative humidity (condensing / non-condensing) |
95% to 100% (2 month / year) / 0 % to 95% |
Maximum operating altitude above MSL8) 1000 m / 2000 m / 3000 m |
● / ○ / ○ (earlier temperature-dependent derating) |
Fresh air consumption |
6500 m³/h |
Features
DC connection |
Terminal lug on each input (without fuse) |
||
AC connection |
With busbar system (three busbars, one per line conductor) |
||
Communication |
Ethernet, Modbus Master, Modbus Slave |
||
Communication with SMA string monitor (transmission medium) |
Modbus TCP / Ethernet (FO MM, Cat-5) |
||
Enclosure / roof color |
RAL 9016 / RAL 7004 |
||
Supply transformer for external loads |
○ (2.5 kVA) |
||
Standards and directives complied with |
CE, IEC / EN 62109-1, IEC / EN 62109-2, BDEW-MSRL, IEEE1547, Arrêté du 23/04/08 |
||
EMC standards |
CISPR 11, CISPR 22, EN55011:2017, EN 55022, IEC/EN 61000-6-4, IEC/EN 61000-6-2, IEC 62920, FCC Part 15 Class A |
CISPR 11, CISPR 22, EN55011:2017, EN 55022, IEC 62920, FCC Part 15 Class A |
|
Quality standards and directives complied with |
VDI/VDE 2862 page 2, DIN EN ISO 9001 |
||
● Standard features ○ Optional |
|
|
|
Type designation |
SC-2500-EV-10 |
SC-2750-EV-10 |
SC-3000-EV-10 |
- At nominal AC voltage, nominal AC power decreases in the same proportion
- Efficiency measured without internal power supply
- Efficiency measured with internal power supply
- Self-consumption at rated operation
- Self-consumption at < 75% Pn at 25°C
- Self-consumption averaged out from 5% to 100% Pn at 35°C
- Sound pressure level at a distance of 10 m
- Values apply only to Permissible values for SMA MV solutions from SMA can be found in the corresponding data sheets.
- AC voltage range can be extended to 753V for 50Hz grids only (option„Aux power supply: external“ must be selected, option “housekeeping” not combinable).
- A short-circuit ratio of < 2 requires a special approval
Other
-
SUNNY CENTRAL UP
The new Sunny Central: more power per cubic meter
-
SUNNY CENTRAL 1850-US / 2200-US / 2500-EV-US / 2750-EV-US
Maximum power density and integration
-
SUNNY CENTRAL 1000CP XT
The most powerful CP with an output of 1 megawatt
- Max. permissible DC voltage: 1000 V
- Nominal AC power (@ 40 °C): 1000 kVA
-
SUNNY CENTRAL 800CP XT / 850CP XT / 900CP XT
The extended CP XT: peak output up to 1 megawatt
- Max. permissible DC voltage: 1000 V
- Nominal AC power (@ 50 °C): 800 kVA / 850 kVA / 900 kVA
-
SUNNY CENTRAL 500CP XT / 630CP XT / 720CP XT / 760CP XT
The extended CP XT: more features included
- Max. permissible DC voltage: 1000 V
- Nominal AC power (@ 50 °C): 500 kVA / 630 kVA / 720 kVA / 760 kVA
-
SUNNY CENTRAL 500CP-JP / 630CP-JP / 800CP-JP / 1000CP-JP
The perfect solution for PV power plants in Japan
- Max. input voltage: 1000 V
- Nominal AC power (@ 50 °C): 455 kVA / 630 kVA / 800 kVA / 900 kVA