Home / Products /

DC/DC CONVERTER TYPE QUINT POWER

  • Manufacturer : Phoenix Contact
  • Guarantee : 12 months
  • Status: In Stock

QUINT DC/DC converter with maximum functionality
DC/DC converters alter the voltage level, regenerate the voltage at the end of long cables or enable the creation of independent supply systems by means of electrical isolation.
QUINT DC/DC converters magnetically and therefore quickly trip circuit breakers with six times the nominal current, for selective and therefore cost-effective system protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical operating states before errors occur.

DIN rail power supply unit, primary-switched mode, 1-phase, output: 24 V DC / 10 A


Width 48 mm
Height 130 mm
Depth 125 mm
Width with alternative assembly 122 mm
Height with alternative assembly 130 mm
Depth with alternative assembly 51 mm
Back to top

Ambient conditions

Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Back to top

Input data

Nominal input voltage range 60 V DC ... 72 V DC
Input voltage range 42 V DC ... 96 V DC
Current consumption 5.6 A (60 V DC)
  4.7 A (72 V DC)
Inrush surge current < 9 A (typical)
Mains buffering > 10 ms (60 V DC)
Input fuse 10 A 150 V DC (internal (device protection))
Type of protection Transient surge protection
Protective circuit/component Varistor
Back to top

Output data

Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 10 A (-40 °C ... 60 °C)
POWER BOOST (IBoost) 12.5 A (-40°C ... 40°C permanent, UOUT = 24 V DC )
Selective Fuse Breaking (ISFB) 60 A (12 ms)
Derating 60 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series yes
Feedback resistance 35 V DC
Protection against surge voltage on the output < 35 V DC
Max. capacitive load Unlimited
Active current limitation 18 A
Control deviation < 1 % (change in load, static 10 % ... 90 %)
  < 2 % (change in load, dynamic 10 % ... 90 %)
  < 0.1 % (change in input voltage ±10 %)
Residual ripple < 20 mVPP
Peak switching voltages nominal load < 10 mVPP (20 MHz)
Maximum power dissipation in no-load condition 4 W (UIN 60 V DC)
Power loss nominal load max. 24 W (UIN 60 V DC)
Back to top

General

Net weight 1 kg
Efficiency > 91 % (UIN 60 V DC / UOUT 24 V DC)
  > 91 % (UIN 72 V DC / UOUT 24 V DC)
Insulation voltage input/output 1.5 kV (type test)
  1 kV (routine test)
Protection class I
Degree of protection IP20
MTBF (IEC 61709, SN 29500) > 1349000 h (25 °C)
  > 765000 h (40 °C)
   
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom

Other